Introduction
Introduction
KDI Power PV Solar Cables are specially designed for connecting photovoltaic power supply systems. These cables are intended for use on the direct current (D.C.) side of photovoltaic systems with a nominal D.C. voltage rating of 1.5 kV.
KDI Power PV Solar Cables are suitable for both indoor and outdoor applications and can be used in flexible as well as fixed installations. Built with high mechanical strength, they perform reliably even in extreme weather conditions. The cables are engineered to withstand demanding environmental conditions in fixed, mobile, rooftop, or architecturally integrated photovoltaic installations.
Application
These cables are suitable for long-term permanent outdoor use, even under harsh and varying climatic conditions. They are designed and tested to operate at a normal maximum conductor temperature of 90°C and can withstand temperatures up to 120°C for up to 20,000 hours. Under normal operating conditions, the expected service life of these cables is approximately 30 years.
Standards
International : 2 Pfg 1169/08.2007 OR EN 50618
Design
- Conductor – Flexible electrolytic tinned fine copper strands in accordance with IEC 60228, Class 5.
- Insulation – Cross-linked, halogen-free and flame-retardant insulation, available in white, red, or black colours.
- Outer Sheath – Cross-linked, halogen-free, flame-retardant sheath with UV and ozone resistance, available in black or black with a red stripe.
Electrical Properties
- Rated DC Voltage: 1.5 kV
- Rated DC Voltage: 1.5 kV
- Maximum Permitted DC Voltage: 1.8 kV
- Maximum Permitted AC Voltage: 1 kV
- Spark Test: 6000 Vac (8400 Vdc)
- Voltage Withstand: 6.5 kV Ac & 15 kV dc
Thermal Characteristics
- Ambient Temperature: -40°C ~ +90°C
- Maximum Temperature at Conductor: 120°C (20000h)
- Short Circuit Temperature: 200°C (at conductor max. 5sec)
- Thermal Endurance Test : According to EN 60216-2 (temperature index +120°C)
Chemical Characteristics
- Mineral Oil Resistance: according to EN 60811-2-1
- Ozone Resistance: according to EN 50396 part 8.1.3 Method B
- Very good resistance to oil and chemicals
- Acid & Alkaline Resistance: According to EN 60811-2-1 (Oxal acid and sodium hydroxide)
- Weathering-UV Resistance
- Resistance to fire:
- Acc. to EN 50618, Table 2
- Single Cable Flame Test: EN 60332-1-2
- Low Smoke Emission: EN 61034-2 (Light Transmittance > 70%)
- Halogen-free per EN 50525-1, Annex B.
Mechanical Characteristics
- Minimum Bending Radius – 6 × OD for fixed installation and 15 × OD for occasional flexing.
- Dynamic Penetration – Designed to meet the required standards for cables used in photovoltaic (PV) systems.
- Tensile Strength – 6.5 N/mm² for insulation and 8 N/mm² for sheathing, in accordance with EN 60811.
- Elongation of Insulation and Sheathing – Minimum 125%, in accordance with EN 60811
- Shrinkage – Maximum 2% at 120°C, in accordance with EN 60811-1-3.
Product & Ratings
| Sr. No. | No. cores x Cross-sec mm² | Outer Dia approx. mm | Single Cable in Air (Amps) | Single Cable On Surface (Amps) | Two loaded cables touching, on a surface (Amps) | Conductor Resistance (Max) Ω/km at 20°C | Approx Cable Weight Kg/Km |
|---|---|---|---|---|---|---|---|
| 2 PfG 1169/08.2007 - PV-F | |||||||
| 1 | 1 x 1.5 | 4.0 | 30 | 29 | 24 | 13.70 | 29 |
| 2 | 1 x 2.5 | 4.4 | 41 | 39 | 33 | 8.21 | 40 |
| 3 | 1 x 4 | 5.0 | 55 | 52 | 44 | 5.09 | 54 |
| 4 | 1 x 6 | 5.6 | 70 | 67 | 57 | 3.39 | 74 |
| 5 | 1 x 10 | 6.5 | 98 | 93 | 79 | 1.95 | 117 |
| 6 | 1 x 16 | 7.6 | 132 | 125 | 107 | 1.24 | 173 |
| BS EN 50618 - H1Z2Z2-K | |||||||
| 1 | 1 x 1.5 | 4.9 | 30 | 29 | 24 | 13.7 | 39 |
| 2 | 1 x 2.5 | 5.3 | 41 | 39 | 33 | 8.21 | 51 |
| 3 | 1 x 4 | 5.9 | 55 | 52 | 44 | 5.09 | 65 |
| 4 | 1 x 6 | 6.5 | 70 | 67 | 57 | 3.39 | 87 |
| 5 | 1 x 10 | 7.4 | 98 | 93 | 79 | 1.95 | 132 |
| 6 | 1 x 16 | 8.8 | 132 | 125 | 107 | 1.24 | 198 |
| 7 | 1 x 25 | 10.5 | 176 | 167 | 142 | 0.795 | 301 |
| 8 | 1 x 35 | 12.0 | 218 | 207 | 176 | 0.565 | 405 |
| 9 | 1 x 50 | 14.0 | 276 | 262 | 221 | 0.393 | 567 |
| 10 | 1 x 70 | 16.0 | 347 | 330 | 278 | 0.277 | 766 |
| 11 | 1 x 95 | 17.8 | 416 | 395 | 333 | 0.210 | 1008 |
| 12 | 1 x 120 | 19.7 | 488 | 464 | 390 | 0.164 | 1253 |
| 13 | 1 x 150 | 22.0 | 566 | 538 | 453 | 0.132 | 1563 |
| 14 | 1 x 185 | 24.5 | 644 | 612 | 515 | 0.108 | 1940 |
| 15 | 1 x 240 | 27.5 | 775 | 736 | 620 | 0.082 | 2481 |
** Higher sizes are also available upon request
Current rating conversion factors for different ambient temperatures
| Ambient Temperature °C | Up to 60 | 70 | 80 | 90 |
|---|---|---|---|---|
| Conversion Factor | 1 | 0.92 | 0.84 | 0.75 |
Why KDI Power Solar Cables